| Technical Item | Specification |
|---|---|
| Switching difference | 4 %RH (±3 % tolerance) - at 50 %RH |
| Permissible air velocity | 50 ft/sec (15 m/s) |
| Contact type | SPDT / change‑over contact |
| Service life | >50,000 cycles |
| Min. switching capacity | 100 mA @ AC/DC 20 V |
| Max. switching capacity | 5 A resistive @ AC 250 V DC 20 W |
| Housing | PC |
| Weight | 60 g |
| Mounting | clip for 35 mm DIN rail |
| Dimensions | 75 × 38 × 50 mm |
| Operating/Storage temperature | -45 to +80 °C |
| Operating/Storage humidity | max.95 %RH (non‑condensing) |
| Protection type | IP20 |
MFR012 Mechanical Hygrostat DIN Rail Humidity Controller
Key Specifications
The NOXT MFR012 mechanical hygrostat is a DIN‑rail mounted humidity switch designed for automatic cabinet humidity management and condensation prevention. It adopts a mechanical sensing structure with an adjustable relative humidity setting range from 40%RH to 90%RH, reliably activating cabinet heaters or cooling fans to stabilize internal humidity and avoid moisture damage to electrical components.
Built with a flame‑retardant PC housing, the MFR012 features high switching capacity, long service life up to over 50,000 switching cycles and IP20 protection class. SPDT change‑over contact enables two‑way control: switching on heaters for dehumidification or starting filter fans for ventilation. Simple 35 mm DIN rail clip‑on installation and clear wiring terminals save on‑site assembly time.






CE · RoHS
Test report per batch
Docs Included
Datasheet + test report
OEM from 100 pcs
CADs, logos, test reporting
Samples
1-5 pcs for qualified buyers
What Buyers Ask Before Inquiry
No. It uses a SPDT changeu2011over contact. The two output terminals work alternatively, either turning on the heater for dehumidification or triggering the cooling fan for ventilation, not simultaneously.
The switching differential is 4%RH with u00b13% tolerance at 50%RH. It will not frequently switch on/off caused by tiny humidity fluctuations inside the cabinet.
No extra power supply for the humidity sensor. It is a fully mechanical hygrostat, relying on the builtu2011in humidityu2011sensitive element to drive the switch contact.